The Omniguard Model 760 multi-spectrum infrared flame detector is designed to detect unwanted fires and output alarm information. The Model 760 senses infrared radiation in five discreet infrared wavelengths for early fire detection for maximum protection. Utilizes the patented Omniguard Fire Event Algorithm for superior false alarm immunity and quick detection of hydrocarbon fueled fires.
Specification
Otis Instruments Omniguard Model 760 Flame Detector
Current Loop (Standard Version): 0 to 20 mA Output
20 mA = Fire
16 mA = Warning Fire IR
5 mA = Warning Ref IR
3 mA = Fire Relay Coil Fault
2 mA = Calibration Not Complete
1 mA = Self-Test Fault
0 ma = Current Loop Fault
4 mA = Normal
Certifications & Approvals:
Class 1, Division 1, Groups B, C & D (Explosion Proof)
Class II, Division 1, Groups E, F & G (Dust Ignition Proof)
TYPE 4X Weatherproof, Dust-Tight, Watertight
CE0081 Ex II 2 G/D
Ex d IIB+H2 T5 Gb for Gas
Ex tb IIIC T100°C Db 1P66 for Dust
Connor-Froo Aluminum Housing Coated to MI.C.5541C Class 3 (White)
Output: Relay
Relays (2): Fire, Trouble, Dry Contacts, Hermetically Sealed
Rated: 2 A at 28 VDC (User Selects NO or NC)
Fire Relay: User Selects Latching or Non-Latching
Optional Accessories:
Swivel Mount - No. 20856
Portable Test Unit - Model 545
Rain Shield - No. 23546
Operating Temperature Range:
-40°F to 185°F (-40°C to 85°C)
Spectral Response:
Infrared Peak Sensitivities: 2.2 um, 3.7 um, 4.4 um, 5.8 um
Nominal Voltage:
24 VDC (Ripple Voltage <240mV)
Voltage Range:
20 to 30 VDC
Power Consumption:
80 mA (Standby), 100 mA (Alarm), 160 mA (Auto and Manual Test)
Digital Output:
RS-485 Modbus Serial 1/0
Product Dimensions:
4.5 × 5.5 x 4.9 in.
Total Weight:
5 Ibs.
Conduit Entry:
3/4-14 NPTF or M20-1.5