Otis Instruments OI-7010-X-X-A4-32-X Hybrid Monitor
Availability: In stock
Specification
Product Type | 32 Channel Gas Monitor |
Operating Voltage | 12V to 35V DC or 120V AC |
Current Draw | 275 mA Maximum at 24 VDC |
Power Supply | 3.13A (75W), 85/264V AC to 24V DC (Optional) |
Antenna Connection | External N-Female Radio Frequency (RF) Connector |
Customizable Settings | Option to Disable Alarm Relays |
Protection | Power Electromagnetic Interference (EMI) Filter |
4-20 mA Surge Suppression | |
RS-485 Surge Suppression | |
Display Screen | 2 Graphical LCD Screens with 128x64 Resolution |
Transflective (Sunlight Readable) with LED Backlight | |
Interface | 5 Push-Buttons (MENU, ADO, SUB, SCAN/HOLD, RESET/ESC) |
Tamb Temperature Range | -40°C to +70°C |
WireFree (Digital), Wired (Analog) Input | Up to 32 Wireless Sensor Inputs, Up to 4 Can Be 4-20 mA Wired Analog Inputs |
Relays | 4 Dry-Contact Relays with 4 Amp Replaceable Fuses |
Individually Set Full Scale, Normally Open or Normally Closed, Latching or Non-Latching, and Fault Terminal | |
Digital Output | RS-485 Modbus |
Product Compatibility | All Otis GEN I and GEN II WireFree Products and Any Wired 4-20 mA Sensors |
WireFree Radio Options |
|
Networks |
|
Enclosure Material | NEMA 4X Fiberglass Enclosure with Clear Window (Available in Stainless-Steel) |
Product Dimensions | 10 in. L x 8 in. W x 6 in. H (Max. Dimensions with Attachments) |
Total Weight | 8.20 lbs. |
Product Mounting | 4 Mounting Feet, 6 in. W x 12-1/4 in. T (included), Maximum Mounting Bolt/Screw Size of 5/16 in. (8mm) Diameter |
Hardware Warranty | 1-Year, Limited |
Part Number Formula | 01-7010-[Power]-[Radio]-A4-32-[Enclosure] |
01-7010-X-X-A4-32 |
Description
The Otis Instruments 0I-7010 Controller is a Hybrid Monitor that supports up to 32 Wireless Sensor inputs. Four of the channels can be setup for 4-20 mA wired input, making the controller compatible with both WireFree and wired sensors. Durable, flexible and customizable, this controller can operate in conjunction with either GEN I or GEN II sensors.
Features
- 32 Channel Hybrid Monitor - Supports WireFree and Up to 4 Wired Sensors
- 12 to 35 VDC Operating Voltage with Optional AC Power Supply
- Operating Temperature Range of -40°C to +70°C
- 5 Push-Button Interface (ADD, MENU, SUB, SCAN/HOLD and RESET/ESC
- Two Graphical LCDs with LED Back Lights
- Radio Options: GEN II 900 MHz or GEN II 2.4 GHz Standard; GEN I 900 MHz Radio Can Also Be Installed
- 4 Individually Configurable Alarm Set-Points - Four Front Panel ALARM LED Indicators (Red); 4 Dry-Contact Relays (4 Amps Maximum per Relay)
- Status LEDs for Power and Fault - Multi-Color Status Light; Amber Fault LED for Indicating System Faults
- Output Options: Wet Contact DC Fault Terminal, Relay 4 Can Optionally Be Configured as a Fault Relay, RS-485 Modbus
- NEMA 4X Standard Fiberglass Enclosure with Clear Window; Optional Stainless-Steel Enclosure with Clear Window
Please refer to datasheet for more information
Technical Data-Sheet