Fisher i2P-100 ElectroPneumatic Transducer

Availability: In stock
Specification
Input Signal:-
  • Available as standard with 4‐20 mA.
  • User configurable by dip switch for split ranging, see table below.
Output Signal(1):-
  • Available as standard 0.2 to 1.0 bar (3 to 15 psig), 0.4 to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar (2 to 33 psig).
  • User configurable by dip switch selection and zero and span potentiometer adjustment, see table below.
Input SignalOutput Pressure
Barpsig
4‐20 mA DC0.2 to 1.03 to 15
0.4 to 2.06 to 30
0.14 to 2.32 to 33
4‐12 mA DC0.2 to 1.03 to 15
12‐20 mA DC0.2 to 1.03 to 15

Equivalent Circuit:-
  • The i2P‐100 equivalent circuit is a series circuit consisting of a constant voltage drop (battery) of approximately 4 VDC and a total resistance of 40 ohms. Input is shunted by two 6.8 V zener diodes
Supply Pressure(1):-
  • Recommended: 0.3 bar (5 psi) higher than upper
  • range limit of output signal
  • Maximum: 3.4 bar (50 psig)

  • Medium: Air or Natural Gas
Maximum Output Air Capacity(3):-
  • 8.0 m3/hr (300 scfh) at 1.4 bar (20 psig) supply pressure
Performance(4):-
  • Reference Accuracy: ±1.0% of full scale output span; includes combined effects of hysteresis, linearity, and deadband.
  • Independent Linearity: ±0.5% of full scale output span.
  • Hysteresis: 0.4% of full scale output span.
  • Frequency Response: Gain is attenuated 3 dB at 3 Hz with transducer output signal piped to a typical instrument input.
  • Temperature Effect: ±0.14% per degrees Celsius (±0.075% per degrees Fahrenheit) of span.
  • Supply Pressure Effect: 0.2% of full scale output span per psi supply pressure change.
  • Vibration Effect: Less than 1% of full scale output span when tested to ISA S75.13.
Operating Ambient Temperature Limits(2):-
  • 40 to 85C (-40 to 185F)
Electrical Seal:-
  • Single sealed device per ANSI/ISA 12.27.01
Electrical Classification:-
  • Hazardous Area:
  • CSA—Intrinsically Safe, Explosion-proof, Type n, Dust‐Ignition proof
  • FM—Intrinsically Safe, Explosion-proof, Type n, Non‐incendive, Dust‐Ignition proof
  • ATEX—Intrinsically Safe, Flameproof, Type n
  • IECEx—Intrinsically Safe, Flameproof, Type n

  • Hazardous Area:
  • When Remotely Vented
  • CSA—Type 4X Encl
  • FM—NEMA 4X
  • ATEX—IP66
  • IECEx—IP66

  • No Remote Venting
  • CSA—Type 3 Encl.
  • FM—NEMA 3
  • ATEX—IP64
  • IECEx—IP64
Other Classifications/Certifications
  • GOST‐R—Russian GOST.R
  • INMETRO— National Institute of Metrology, Quality, and Technology (Brazil)
  • KGS—Korea Gas Safety Corporation (South Korea)
  • NEPSI—National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation (China)
  • RTN—Russian Rostekhnadzor
  • RTN—Russian Rostekhnadzor
  • Contact your Emerson Process Management sales office for classification/certification specific information
Connections
  • Supply and Output Pressure: 1/4 NPT internal connection
  • Vent: 1/4 NPT internal
  • Electrical: Standard 1/2 NPT
  • Wire Size: 18 to 22 AWG
Connections
  • Zero and Span:Trim potentiometers (20 turn) for zero and span adjustments are located under the housing cap.
  • Switch: Allows input signal split range and user‐configurable 0.14 to 2.3 bar output.
Mounting Position
  • Actuator
  • pipestand or
  • surface
Approximate Weight (Transducer Only)
  • 2.5 kg (5.5 lbs)
Description

Fisher® i2P-100

Fisher® i2P-100 electro-pneumatic transducer uses a patented converter module that converts a milliampere input to a proportional pressure output. Both the current input and pressure output range are user-configurable in the field. The converter module uses small parts of minimum mass, which are balanced symmetrically around a pivot point at the center of the mass. This balanced arrangement results in a high performance instrument that reduces sensitivity to vibration. An integral pneumatic relay provides the high capacity necessary to drive pneumatic control valve/actuator assemblies without additional boosters or positioners. The transducer also provides stable, accurate operation when its output is transmitted to small volume chambers, such as a pneumatic positioner or other pneumatic instrument. Reduced sensitivity to vibration, combined with high capacity and first order lag characteristics, make the i2P-100 transducer suitable for direct mounting on control valve/actuator combinations.

  • Low Pneumatic Supply Consumption—The transducer has low pneumatic supply consumption which lowers operating costs.
  • Split Range—Selectable user field-configurable two-way split range, using either half of the standard input signal.
  • Tolerant of Dirty Supply Medium—Free-flow pilot stage design and large internal air passages provide excellent tolerance to dirty pneumatic supply, by reducing the effects of contaminant buildup and erosion. The removable primary orifice and replaceable 5 micron filter are easy to remove for service and maintenance.